Cold Storage Pioneer in Industrial Design
Cold Room Panels form the insulated enclosure of a refrigerated facility. Selecting them requires a coordinated specification for thermal performance, joints, surface finishes, structural loads and installation details. The right combination depends on the room temperature, surrounding conditions, cleaning procedures and daily handling operations.
A freezer storing packaged meat has different requirements from a chilled vegetable room. A food preparation area washed every evening creates different demands from a warehouse holding sealed cartons. Even two rooms operating at the same temperature may need different panel specifications because their locations, traffic and construction details differ.
For the buyer, these differences matter before an order is placed. Panel thickness affects insulation and usable space. Floor construction affects vehicle access. Ceiling spans influence support requirements. Joint details determine how effectively the completed enclosure resists air and moisture entry.
This guide explains the decisions that deserve attention when specifying Cold Room Panels for a new facility, an extension or a replacement project.
Start with a written description of how the room will operate.
“Frozen food storage” leaves several important questions unanswered. Will products arrive already frozen? Will warm products occasionally enter? Will the room operate continuously? Does the door open into an air-conditioned packing area or a loading bay exposed to outdoor humidity?
The following information should accompany a panel enquiry.
| Project information | What to establish |
|---|---|
| Room duty | Chilled storage, frozen storage, processing or rapid freezing |
| Operating temperature | Normal setpoint and expected operating range |
| Surrounding conditions | Temperature and humidity beside each wall and above the ceiling |
| Dimensions | Whether measurements are internal clear dimensions or external dimensions |
| Product handling | Pallets, shelving, trolleys, pallet trucks or forklifts |
| Cleaning | Chemicals, wash temperature, frequency and application method |
| Location | Inside an existing building or exposed to outdoor weather |
| Future changes | Expansion, new equipment or a possible change in operating temperature |
The distinction between internal and external dimensions deserves particular attention. A thicker wall panel reduces clear space when the building footprint remains fixed. Door clearances, rack positions and handling aisles should therefore be checked against the finished internal dimensions.
Future use should also be discussed early. Converting a chilled room into a freezer can require changes to the floor, vapour-control details, doors and refrigeration system. Record that possibility in the initial design brief.
An insulated metal panel normally combines an insulation core with two metal facings bonded to it. The core, facings and bond work together; specifying only the foam thickness leaves much of the product undefined. The Metal Construction Association describes this composite construction in its selection guidance for insulated metal panels. metalconstruction.org
PUR and PIR identify different insulation formulations. A useful comparison should examine the declared performance of the finished products:
Core density can help identify a specification, but it provides an incomplete picture of thermal, structural and fire performance.
Ask the supplier to identify the exact product being offered. Statements such as “high-density insulation” or “premium panel” should be accompanied by measurable properties and supporting documentation.
TunelGroup’s published cold room wall panel range includes polyurethane-core panels in 50, 60, 80, 100, 120, 150 and 200 mm thicknesses. The project enquiry should identify which thickness, facing and joint configuration is required. Tunelgroup Cooling Systems
Thickness is a useful purchasing description. Thermal performance determines how much heat passes through the enclosure.
Three terms commonly appear in technical documents:
| Property | Meaning | How to compare it |
|---|---|---|
| Thermal conductivity, λ | How readily heat travels through a material | Lower values indicate better insulation at comparable test conditions |
| Thermal resistance, R | Resistance to heat flow through a layer or assembly | Higher values indicate greater resistance |
| Thermal transmittance, U | Heat transfer through a defined assembly per unit area and temperature difference | Lower values indicate less heat transfer |
Check whether a quoted U-value describes the panel centre, includes joint effects, or represents a more complete assembly. Compare values calculated using equivalent assumptions.
The steady-state transmission calculation used in the ASHRAE refrigerated-facility load guidance is:
Q = U × A × ΔT
Where Q is heat transfer in watts, U is thermal transmittance in W/m²·K, A is area in m², and ΔT is the temperature difference in kelvins. handbook.ashrae.org
Consider a freezer with:
Assume two alternative panel specifications have the following U-values:
| Calculation | Option A | Option B |
|---|---|---|
| Assumed U-value | 0.25 W/m²·K | 0.18 W/m²·K |
| Area | 500 m² | 500 m² |
| Temperature difference | 53 K | 53 K |
| Calculated transmission load | 6.625 kW | 4.770 kW |
The calculated difference is 1.855 kW of thermal load.
If these conditions remained constant for 24 hours, the difference would equal approximately 44.5 kWh of heat entering the room. The corresponding electricity consumption depends on refrigeration efficiency and operating conditions.
These are illustrative assumptions, independent of any particular TunelGroup product or thickness. The calculation excludes floors, doors, additional thermal bridges and air leakage.
Compare the available thicknesses using their declared thermal performance, installed cost, space requirements and expected operating conditions.
Include electricity tariffs, operating hours and refrigeration efficiency when evaluating the financial benefit of improved insulation. For outdoor installations, assess weather exposure and solar effects separately.
The complete equipment selection must also include product cooling, air infiltration, internal gains and refrigeration equipment loads. TunelGroup’s Cold Room Load Calculation Guide explains that broader calculation.
Cold Room Panels meet at corners, ceilings, floors, door frames and service openings. These junctions deserve the same design attention as the main panel surfaces.
Warm, moisture-laden air entering a cold enclosure can produce condensation or ice. Moisture reaching the insulation can impair its performance. ASHRAE therefore emphasises continuity of the vapour-retarding envelope, particularly at joints and penetrations. handbook.ashrae.org
Before installation, identify the sealing detail for:
In typical cold-store conditions, vapour control requires particular attention on the warmer side of the insulation. The precise seal arrangement should follow the approved system drawings.
Cam-locks help pull panels together. The specified gaskets and sealants complete the joint’s sealing function.
Every later modification should follow the same discipline. Adding a cable through a finished wall creates another penetration that needs a durable, compatible seal.
A panel finish should be selected against the conditions it will encounter.
A dry storage room holding sealed cartons may have a relatively mild cleaning regime. A meat handling room can experience frequent washing, splashing, chemical exposure and trolley impacts.
The Codex General Principles of Food Hygiene calls for durable, maintainable construction and surfaces that can be cleaned effectively. It also addresses layouts and overhead construction that reduce contamination risks. fao.org
Before selecting the facing, give the supplier the proposed detergent and disinfectant details, including concentration, contact time, application temperature and rinsing procedure.
Request confirmation of compatibility for the coating, exposed metal, sealants and trims. Where stainless steel is proposed, specify the grade and finish.
Practical details matter just as much as the sheet material. Wall bases should be accessible for cleaning. Protective rails should avoid creating inaccessible dirt traps. Exposed insulation edges need suitable closures.
The phrase “food-grade panel” should be supported by documentation relevant to the intended application and exposure.
Floor selection requires a separate load assessment.
A uniformly distributed load rating describes a different condition from a loaded pallet truck turning on small wheels. Rack feet concentrate weight into limited areas. Forklifts introduce wheel loads, braking forces and repeated traffic.
Manufacturers distinguish between modular floors and heavier-duty constructions according to these operating demands. KPS Global
Provide:
Ask for written confirmation that the complete floor assembly suits those conditions, including its supporting base.
TunelGroup’s cold room floor panels should be evaluated against the intended handling equipment and floor layout. Some applications require an engineered insulated concrete floor or an approved load-distributing construction.
For below-zero rooms over ground, also assess the possibility of freezing beneath the floor and resulting frost heave. Underfloor heating or another engineered prevention method may be required. handbook.ashrae.org
Complete the floor design before fixing door elevations. Thresholds, finished floor levels and vehicle access are difficult to correct after installation.
A panel ceiling needs a defined structural arrangement.
Confirm the clear spans, support positions, attachment details and permitted loads for the selected panel. Maintenance access and suspended equipment require explicit consideration; insulated ceilings may need dedicated supports. handbook.ashrae.org
The coordination drawing should show who supports each item:
| Component | Detail to resolve |
|---|---|
| Ceiling panels | Span, bearings, hangers and connections |
| Evaporators | Equipment supports and service clearances |
| Pipework and cable trays | Support routes and insulated penetrations |
| Door assemblies | Frame support, opening reinforcement and threshold |
| Maintenance access | Approved walkways or access arrangements |
| Room pressure control | Required devices and their installation details |
Heavy equipment should have an approved load path. Any attachment to the panel assembly needs a documented detail.
Door openings should be coordinated with trolley and pallet dimensions, turning space and the finished floor level. An opening that works on a plan can still restrict handling once frames, protective barriers and equipment are installed.
The layout should also preserve evaporator airflow and service access. Coordinate the enclosure with the selected refrigeration units before panel production begins.
Fire documentation should identify the exact panel construction and the conditions under which its classification applies.
Two terms frequently appear in specifications:
| Term | What it addresses | Relevant European classification reference |
|---|---|---|
| Reaction to fire | A product’s behaviour when exposed to fire | EN 13501-1 |
| Fire resistance | An element’s ability to maintain specified functions during fire exposure | EN 13501-2 |
These are separate assessments. BSI describes their respective scopes in its guidance for EN 13501-1 and EN 13501-2. knowledge.bsigroup.com
Check the classification report against the proposed core, thickness, facings, joints, orientation and installation arrangement. Confirm that openings and service penetrations are addressed where relevant.
For each proposed product, request the applicable:
EN 14509 covers specified factory-made metal-faced insulating panels, including cold-store applications for walls and ceilings. Its scope should be checked against the actual product and intended use. knowledge.bsigroup.com
Agree the required documentation with the project designer and relevant approving parties before purchasing.
A detailed specification becomes useful when the delivered and installed work can be checked against it.
Confirm the base is suitable, dimensions match the approved drawings and panel identification corresponds to the delivery schedule. Inspect facings, edges and joints for transport damage.
Resolve discrepancies before panels are concealed by trims or adjacent construction.
Follow the approved sequence for alignment, locking, sealing and fixing. Inspect seals while they remain visible.
Remove drilling and cutting debris promptly. Metal filings left on panel surfaces can oxidise, stain the finish and contribute to coating damage. Use the manufacturer’s approved cleaning methods and avoid tools that abrade the coating. metlspan.com
Protect the finished surfaces from subsequent trades. Equipment installation often introduces additional penetrations, impact damage and unapproved fixings.
The handover package should include drawings, product references, maintenance instructions and photographs of concealed junctions.
Check doors, thresholds, exposed seals and service penetrations. During initial operation, investigate localised condensation or frost and confirm the cause before accepting the installation.
Record how future repairs and penetrations should be carried out. This gives maintenance personnel a practical reference when the room is modified.
| Recommended | Not Recommended |
|---|---|
| Compare declared thermal performance under equivalent assumptions | Choose exclusively by nominal thickness |
| Confirm wheel loads and rack loads | Treat a distributed floor rating as a vehicle rating |
| Coordinate supports and service openings before manufacture | Leave major structural details to site improvisation |
| Match finishes to documented cleaning conditions | Select a coating solely by colour or appearance |
| Check the scope of fire classifications | Infer a complete fire rating from the insulation name |
| Inspect joints before they are concealed | Rely only on a final visual inspection |
| Compare complete installed scopes | Compare quotations using panel price per m² alone |
A useful quotation should make its quantities and assumptions visible.
Check whether the quoted area includes walls, ceilings, partitions and floors. Establish how door openings are treated, whether cutting waste is included and which dimensions form the basis of measurement.
For a facility with several rooms, prepare a partition schedule. A shared partition is one physical assembly, although its temperature exposure and structural requirements still need assessment.
Then compare the accompanying scope: trims, sealants, fixings, supports, doors, protective elements, packaging, transport, unloading, installation and commissioning responsibilities.
An apparent price difference may reflect a substantial difference in what is being supplied.
A productive enquiry starts with a drawing and an operating brief.
Send TunelGroup the room layout, country and installation location, temperature requirements, surrounding conditions, door schedule and handling equipment details. Include cleaning requirements and any required technical classifications.
For an existing facility, photographs of the floor, roof structure, access route and service connections help clarify installation constraints.
The TunelGroup wall panel range provides a starting point for discussing thickness and construction. The quotation should then identify the proposed configuration, included accessories and interfaces with the floor, doors and refrigeration equipment.
This approach gives the buyer a specification that can be reviewed, compared and checked during installation.
Select thickness using the declared thermal performance, operating temperature, surrounding conditions and project requirements. Include structural demands and the economic value of reduced heat transmission.
Use a construction specifically approved for the floor application. Floor suitability depends on the complete assembly, support conditions, surface finish and expected point or rolling loads.
Evaluate the reduction in transmission load against the additional installed cost. Operating hours, temperature difference, electricity tariffs and refrigeration efficiency influence the result.
Inspect their condition and confirm the original specification, joint compatibility and suitability for the new room. Damaged facings, wet insulation, altered joints or missing identification may limit reuse.
Record its location and the surrounding temperature and humidity. Investigate joints, door seals, penetrations, thermal bridges and operating conditions. The repair should address the identified cause.
Well-specified Cold Room Panels connect the thermal, structural and hygienic requirements of a refrigerated facility.
The most useful purchasing documents show how those requirements will be met: declared thermal properties, coordinated drawings, suitable floor construction, verified supports, sealing details and a clear installation scope.
Resolve these decisions before manufacture. They determine how effectively the enclosure can be installed, maintained and adapted throughout its service life.